Inlet Fogging Sizing
Moisture (GPM) required to lower inlet temperature
Data:
Temperature Dry Bulb: 110°F
Temperature Wet Bulb: 70°F
Turbine Air Flow: 745,388 ft3/min
From Table (See Above):
Humidity Ratio: 64 grains/(lb dry air)
Specific Volume: 13.75 ft3/(lb dry air)
Calculation:
(745,388 ft3/min)(64 grains/lb. of dry air) |
= 59.7 GPM 60 GPM |
(7000 grains/lb. of water)(13.75 ft3/lb. of dry air)(8.3lbs/gallon) |